Description
Morley High Sensitivity Single Channel FAAST XS Aspiration Unit (170m 20 holes)
The FAAST XS aspirating smoke detector combines advanced particle separation with unique dual source optical smoke detection technology to provide highly sensitive Very Early Warning Fire Detection while providing enhanced immunity to false alarms. This technology enables FAAST XS to accurately detect incipient fire conditions up to Class A (according to EN54-20), in applications ranging from mission critical to harsh and extreme environments.
An installed FAAST XS device can administrate up to 170 m pipe length in standard coverage type applications and can be monitored in several different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a direct connection, or via FAAST XS’s onboard USB. When connected to a L AN, FAAST XS’s email server can provide email event notification to appropriate personnel. FAAST XS also communicates alarm and notifications via relays.
Key Features:
Approved for use in Class A, B and C, according to EN54-20
Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration
Three alarm levels and three sensitivity modes provide application flexibility
User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter
Easy configuration via USB interface, no external power needed
Configurable air flow fault thresholds and verification period
Convenient wiring compartment