//Spectrex SharpEye 40/40I Triple IR (IR3) Flame Detector

Spectrex SharpEye 40/40I Triple IR (IR3) Flame Detector

Multi spectrum design – for long distance detection and high false alarm immunity

Sensitivity selection – to ensure no zone crossover detection

Automatic and Manual Built-In-Test (BIT) – to assure continued reliable operation

Heated window – for operation in harsh weather conditions (snow, ice, condensation)

Multiple output options for maximum flexibility and compatibility: Relays (3) for Alarm, Fault and Auxiliary – 0-20mA (stepped) – HART Protocol for maintenance and asset management – RS-485, Modbus Compatible

High Reliability – MTBF – minimum 150,000 hours

Approved to Safety Integrity Level 2 (SIL2 – TUV)

5-Year Warranty

User Programmable via HART or RS-485

Hazardous area zones: Zones 1 & 2 with IIC gas group vapors present – Zones 21 & 22 with IIIC dust type present

Ex approved to: ATEX & IECEx – FM/FMC/CSA – TR CU (EAC)

3rd party performance tested: EN54-10 (VdS) – FM3260

Marine Approval – MED ‘Wheelmark’ approval (DNV); Offshore Oil & Gas installations

Onshore Oil & Gas installations and pipelines

Chemical plants

Petrochemicals plants

Storage Tank farms

Aircraft hangars

Power Generation facilities

Pharmaceutical Industry

Printing Industry

Warehouses

Automotive

Explosives & Munitions

Waste Disposal facilities; Spectrex 40/40I – Data Sheet

Spectrex 40/40I – User Guide

Spectrex 40/40I – Accessories

SKU: convhazard370 Category: Tag:

Description

Spectrex SharpEye 40/40I Triple IR (IR3) Flame Detector

The new 40/40I, a multi spectrum based on three IR bands (IR3), detects fuel and gas fires at long distances with the highest immunity to false alarms. The 40/40I IR3 can detect a 1 ft2 (0.1m2) gasoline pan fire at 215 ft (65m) in less than 5 seconds. The 40/40I is the most durable and weather resistant flame detector currently on the market.

Its new features include a heated window, to eliminate condensation and icing; HART capabilities for digital communications; lower power requirements; and a compact, lighter design. Due to increased reliability, the 40/40 Series warranty period has been extended to 5 years and is SIL2 (TUV) approved to IEC 61508.

Key Features:

Multi spectrum design – for long distance detection and high false alarm immunity

Sensitivity selection – to ensure no zone crossover detection

Automatic and Manual Built-In-Test (BIT) – to assure continued reliable operation

Heated window – for operation in harsh weather conditions (snow, ice, condensation)

Multiple output options for maximum flexibility and compatibility: Relays (3) for Alarm, Fault and Auxiliary – 0-20mA (stepped) – HART Protocol for maintenance and asset management – RS-485, Modbus Compatible

High Reliability – MTBF – minimum 150,000 hours

Approved to Safety Integrity Level 2 (SIL2 – TUV)

5-Year Warranty

User Programmable via HART or RS-485

Hazardous area zones: Zones 1 & 2 with IIC gas group vapors present – Zones 21 & 22 with IIIC dust type present

Ex approved to: ATEX & IECEx – FM/FMC/CSA – TR CU (EAC)

3rd party performance tested: EN54-10 (VdS) – FM3260

Marine Approval – MED ‘Wheelmark’ approval (DNV)

Applications:

Offshore Oil & Gas installations

Onshore Oil & Gas installations and pipelines

Chemical plants

Petrochemicals plants

Storage Tank farms

Aircraft hangars

Power Generation facilities

Pharmaceutical Industry

Printing Industry

Warehouses

Automotive

Explosives & Munitions

Waste Disposal facilities; Spectrex 40/40I – Data Sheet

Spectrex 40/40I – User Guide

Spectrex 40/40I – Accessories