//Apollo AlarmSense Open Area Sounder – 55000-018APO

Apollo AlarmSense Open Area Sounder – 55000-018APO

Key Features:

Sound output of up to 99dB

LPCB approved

Separate first-fix base for ease of installation

IP65 rated (outdoor use)

Designed for use as part of an AlarmSense fire alarm panel system

Wall mounted

Tone synchronisation

Monitors the presence of the sounder head

SKU: ApolloFD42 Category: Tag:

Description

Apollo AlarmSense Open Area Sounder – 55000-018APO

The AlarmSense open area sounder has an IP65 rating, meaning that it is suitable for outdoor use. In the event of unauthorised sounder head removal, the unit generates a fault warning but all other devices on the same zone will continue to operate.

Brand Information

AlarmSense is a range of conventional fire detection and alarm products designed to be connected to the same pair of supply wires, making installation quicker and less expensive.

AlarmSense has been developed to make the design and installation of a fire detection and alarm system easier and more economic for small to medium-sized buildings. The range also allows an existing system to be extended or modified if necessary. This flexibility makes AlarmSense an excellent choice for use in HMOs (House in Multiple Occupation).

As you would expect from Apollo, AlarmSense incorporates features that help reduce false alarms and patented technology to ensure the integrity of a system. The range also includes products, such as beacons, to help meet the requirements of the Disability Discrimination Act (DDA).

Brand Features

AlarmSense sounders and manual call points are fitted to the same zone as detectors. In quiescent state, the zone is powered at between 9V and 15V, nominally 12V, at which only detectors and call points operate. Sounders require 24V to operate.

When an alarm is detected on a zone, the control panel increases the line voltage to 24V on that zone causing the sounders to produce a continuous ‘Evacuate’ sound. Any voltage-sensitive output devices – relay modules or other alarm devices – also operate.

When the voltage is increased to 24V, the detector alarm current will reduce to 1.5mA. The detectors are latched in alarm until they are reset by reducing the voltage to less than 2V for greater than 1 second. Output devices will de-activate each time the voltage is reduced to 12V unless otherwise stated in their specification.

It is possible to generate an ‘Alert’ tone by pulsing the supply voltage from 12V to 24V and the sounders configured to continuous output. Pulse frequency of 1 second on, 1 second off, is recommended for compliance with BS5839 Pt1.