/Aspirating Smoke Detectors
  • Patented venturi pipe and duct housing One-pipe air sampling system Uniguard Superflow New cross-section (shape) of the venturi pipe gives an optimum of venturi effect Test hole on cover Simple installation Sensitive flow indicator Simple service and maintenance Installer-friendly connection of cables Foolproof installation of venturi pipe
    Details
  • Economical, single or dual area aspirated ‘fire’ detection 1 or 2 sampling pipes - each up to 100m in length Coverage up to 1,500m at class C 3 users configurable alarm levels per channel Integral Display and Programmer Rugged IP65 enclosure Single, redundant or coincidence detection strategies
    Details
  • Economical, single or dual area aspirated ‘fire’ detection 1 or 2 sampling pipes - each up to 100m in length Coverage up to 1,500m at class C 3 users configurable alarm levels per channel Integral Display and Programmer Rugged IP65 enclosure Single, redundant or coincidence detection strategies
    Details
  • Economical, single or dual area aspirated ‘fire’ detection 1 or 2 sampling pipes – each up to 50m in length Uses conventional or analogue addressable detectors (not supplied) Detection element can be serviced or replaced Rugged IP65 enclosure
    Details
  • Economical, single or dual area aspirated ‘fire’ detection 1 or 2 sampling pipes – each up to 50m in length Uses conventional or analogue addressable detectors (not supplied) Detection element can be serviced or replaced Rugged IP65 enclosure
    Details
  • Single & Dual channel versions with independent channels including fan, sensor, and flow monitoring Multiple event logging up to 2240 events Ultrasonic airflow sensing PipeIQâ„¢LT software provides intuitive system layout and configuration all in one package User friendly air flow pendulum graph for verification of pipe network functionality Protected electronics from air flow and accidental damage during installation or maintenance Easily replaceable and reusable filter without affecting the rest of the device Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no special tools required. Easy access to parts requiring routine maintenance IP65 enclosure
    Details
  • Single & Dual channel versions with independent channels including fan, sensor, and flow monitoring Multiple event logging up to 2240 events Ultrasonic airflow sensing PipeIQâ„¢LT software provides intuitive system layout and configuration all in one package User friendly air flow pendulum graph for verification of pipe network functionality Protected electronics from air flow and accidental damage during installation or maintenance Easily replaceable and reusable filter without affecting the rest of the device Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no special tools required. Easy access to parts requiring routine maintenance IP65 enclosure
    Details
  • Approved to EN 54-20 in Class A, B and C Provides Very Early Warning Fire Detection, as precise as 0,00095 %/m Five alarm levels and three sensitivity modes provide application flexibility User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption Ultrasonic flow sensing for each pipe inlet and chamber airflow monitoring for precise system health information Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions Easy configuration via USB interface, no external power needed Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications
    Details
  • Approved for use in Class A, B and C, according to EN54-20 Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration Three alarm levels and three sensitivity modes provide application flexibility User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter Easy configuration via USB interface, no external power needed Configurable air flow fault thresholds and verification period Convenient wiring compartment
    Details
  • Detection as precise as 0.0015%/m obscuration Integral Ethernet interface enables remote monitoring and e-mail status updates Patented particle separator and field-replaceable filter remove contaminants from the system Five alarm levels & two sensitivity modes Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement Protects up to 2,000 square metres Advanced detection algorithms reject common nuisance conditions PipeIQâ„¢ software provides intuitive system layout, configuration, and monitoring all in one package Fault indictors covering a broad spectrum of events Unique air flow pendulum graph verifies pipe network functionality Particulate graph displays subtle environmental changes for early problem indications
    Details
  • IT areas and clean rooms General warehouses High bay storage areas Production and assembly lines Wind farms Libraries, museums and archives Hospitals, hotel rooms and saunas Recycling areas Rail vehicles and tunnels Cold stores/freezers
    Details
  • IT areas and clean rooms General warehouses High bay storage areas Production and assembly lines Wind farms Libraries, museums and archives Hospitals, hotel rooms and saunas Recycling areas Rail vehicles and tunnels Cold stores/freezers
    Details